Tuesday, April 01, 2008

Scissor Stairs




Q: What is a Scissor Stair? When are Scissor Stairs permitted? Will Scissor Stairs still be permitted under the New NYC Construction Code?


A: A Scissor Stair is a set of 2 interlocking stairways providing two separate paths of egress located within one stairwell enclosure. The Stairs wind around each other, and are separated from each other within the enclosure, by fire rated construction having the same rating as the Stair Enclosure (usually 2-hour construction). Scissor Stairs are permitted under certain conditions by the New NYC Construction Code, as listed below.

Scissor stairs are particularly effective in small footprint Residential Apartment buildings requiring 2 vertical means of egress. In large footprint buildings, Scissor Stairs may create Dead End Corridors, and should be avoided.

Scissor Stairs are permitted in:

'J-2' Residential Apartment Buildings ('R-2' New Const Code).
Per New Construction Code Section 1014.2.1:




  • Stair doors must be at least 15 feet apart from each other


  • Stair Enclosing Walls shall be Constructed of 2-Hr rated Masonry or approved Masonry Equivalent material.


  • Stair may share common walls, floors, ceilings or scissor stairs assemblies or other enclosures provided that the construction separating the stairs is also of at least a 2-hour fire resistance rating and constructed of masonry or masonry equivalent.


  • Author’s Note: Comply with Dead End Corridor limitations.


  • Author’s Note: Both Stairs within the Scissor Stair enclosure must extend to the Roof to provide Roof Access.


  • Author’s Note: When both of the Stairs within a Scissor Stair terminate at a Street Floor Lobby, egress must be provided in 2 separate directions from the Lobby to the Street.



'E' Office Buildings ('B' New Const Code)
Per New Const Code Requirements Section 1014.2.1:




  • With a Building Height not exceeding 60 feet


  • With a Footprint not exceeding 2,000 sq ft per floor


  • Stair doors shall be at least 15 feet apart from each other


  • Maximum travel distance of 50 feet from most remote point to a Stair Door


  • Stair Enclosing Walls shall be Constructed of 2-Hr rated Masonry or approved Masonry Equivalent material


  • Stair may share common walls, floors, ceilings or scissor stairs assemblies or other enclosures provided that the construction separating the stairs is also of at least a 2-hour fire resistance rating and constructed of masonry or masonry equivalent.


Have a question? E-mail Permitadvisor

Saturday, March 29, 2008

Minimum Trap/Waste Outlet Sizes for Plumbing Fixtures

Q: What are the Minimum Trap/Waste Outlet Sizes for Plumbing Fixtures, the the NYC Building Code?

A: Refer to Table 16-6 for the Minimum Trap Sizes, as restated below:

Fixtures & Trap Sizes:
Bathtub (with or without overhead Shower 1 1/2"
Bidets 1 1/2"
Combination Sink and Wash (Laundry Tray) 2"
Dental Unit or Cuspidor 1 1/2"
Drinking Fountain 1 1/2"
Dishwasher, Commercial 2"
Dishwasher, Domestic 1 1/2"
Floor Drain 3"
Funnel Drain 1 1/2"
Kitchen Sink, Domestic 2"
Laboratory Cup Sink 1 1/2"
Laboratory Sink 2"
Lavatory, Common 1 1/2"
Lavatory, Barber, Beauty Parlor, or Surgeon's 1 1/2"
Lavatory, multiple type (was fountain or sink) 1 1/2"
Laundry Tray (1 or 2 compartments) 1 1/2"
Laundry Standpipe 2"
Shower, Stall 2"
Shower, Gang 3"
Sink (Surgeon's) 1 1/2"
Sink (flushing rim type, flush valve supplies) 3"
Sink (service type with Trap Standard) 3"
Sink, Commercial (Pot, Scullery or sim) 2"
Sterilizers 3"
Urinal (Pedestal) 3"
Urinal (Stall Type) 2"
Urinal (Wall Lip Type) 2"
Urinal (Women's) 3"
Water Closet (Waste Outlet) 3"

Have a question? E-mail Permitadvisor

Wednesday, February 06, 2008

When is a Work Permit Required?

Q: When exactly is a Work Permit required from the NYC Department of Buildings for construction work?

A: The Code allows 'Minor Alterations' and 'Ordinary Repairs' to buildings without the need to obtain a Work Permit provided that it meets their definition of same.

Minor Alterations and Ordinary Repairs do not include the following and therefore require the issuance of a Work Permit:

  • Cutting away of any portion of a wall, floor, or roof construction.
  • Removal, cutting, or modification of any beams or structural supports.
  • Removal, change, or closing of any required means of egress
  • Rearrangement or relocation of any parts of the building affecting loading or exit requirements
  • Alterations, modifications, replacements, repair or removal of Sprinkler or Standpipe systems.
  • Alterations, modifications, replacements, repair or removal of Plumbing or Sewer systems. However, replacement of Plumbing Fixtures on existing Roughing from the inlet side of a trap to any exposed stop valve does not require a Permit.
  • Any other work affecting health or the fire or structural safety of the building.
Below are the Code Sections specifying the requirements. In certain instances, this information may not be sufficient to characterize the work, and additional research for Permit requirements may be necessary, especially with exterior work.

ARTICLE 5 MINOR ALTERATIONS: ORDINARY REPAIRS

27-124 Minor alterations
For the purposes of this code, the term "minor alterations" shall mean minor changes or modifications in a building or any part thereof, excluding additions thereto, that do not in any way affect health or the fire or structural safety of the building. Minor alterations shall not include any of the work described or referred to in section 27-126 of this article, or any other work for which a permit is required under the provisions of articles ten through seventeen of this subchapter.

27-125 Ordinary repairs
For the purposes of this code, the term "ordinary repairs" shall mean replacements or renewals of existing work in a building, or of parts of the service equipment therein, with the same or equivalent materials or equipment parts, that are made in the ordinary course of maintenance and that do not in any way affect health or the fire or structural safety of the building or the safe use and operation of the service equipment therein. Ordinary repairs shall not include any of the work described or referred to in section 27-126 of this article or any other work for which a permit is required under the provisions of articles ten through seventeen of this subchapter.

27-126 Work not constituting minor alterations or ordinary repairs.
(a) For the purposes of this code, minor alterations or ordinary repairs shall not include the cutting away of any wall, floor, or roof construction, or any portion thereof; or the removal, cutting, or modification of any beams or structural supports; or the removal, change, or closing of any required means of egress; or the rearrangement or relocation of any parts of the building affecting loading or exit requirements, or light, heat, ventilation, or elevator requirements; nor shall minor alterations or ordinary repairs include additions to, alterations of, or rearrangement, relocation, replacement, repair or removal of any portion of a standpipe or sprinkler system, water distribution system, house sewer, private sewer, or drainage system, including leaders, or any soil, waste or vent pipe, or any gas distribution system, or any other work affecting health or the fire or structural safety of the building.

(b) Minor alterations or ordinary repairs shall include the repair or replacement of any fixture, piping or faucets from the inlet side of a trap to any exposed stop valve.

Have a question? E-mail Permitadvisor

Landmarks Expedited Review

Q: What is the criteria necessary to file for a Landmarks Expedited Review Permit?

A: Landmarks Approval for construction projects can add significant lead time to issuance of a Work Permit. Landmarks offers an Expedited Review process for Alterations meeting the below criteria. We encourage all applicants that can comply with the criteria to submit their application using this method:

1. Must be INTERIOR WORK ONLY;
2. Must be performed ONLY ABOVE THE SECOND STORY;
3. Must NOT be performed on any portion of a space designated as an interior landmark;
4. Must NOT involve any change to, replacement of, or penetration of any window, skylight,
exterior wall or roof of any portion thereof; and
5. For floors 3 through 6 must NOT involve a dropped ceiling or a partition which is less than a
minimum of 1'-0" back from any interior windows sill or frame, whichever is further from the
glass.

Have a question about Landmarks Permits? E-mail Permitadvisor

Friday, November 16, 2007

Asbestos ACP-5 Exemptions

Replacement of a Rooftop Air Conditioner with no change to Ductwork is exempt from the filing of an Asbestos Report ACP-5.

Q:
I am filing my alteration with the NYC Department of Buildings for Permit Issuance. Are there any types of alterations that are exempt from the filing of an ACP-5 Asbestos Report? If so, what is the list of exempted items?

A: As per a previous post, Buildings filed with the DOB after April 1, 1987 do not require an Asbestos Investigation (ACP-5). In addition, the following items are exempt:

Accessory Parking
Awnings
Building-Sealing
Candy or News Stands
Change of Use, Legalization, or Certificate of Occupancy requiring No Work
Concrete Work (Exterior)
Cranes
Curb Cuts
Debris Chutes, where chute will not be used for Asbestos-Containing Materials
Demolition of 1 story Garages, maximum capacity 2 cars, NOT supplied with Water Lines
Dumbwaiter-Sealing
Elevator Equipment (not including construction and enclosure of Elevator Shaft)
Emergency Power NOT involving hard wiring (i.e. Battery Packs)
Finish Material Installation
Fire Escape Installation
Flagpoles
Greenhouses-Detached
Hoist
Interior Non-Bearing Partition Installation involving NO penetration of Hung Ceiling
Kiosks
Legalization of Demolition Work which occurred prior to 4/1/1987
Parapet Walls
Radio Antennas (Towers)
Relocating Parking Lot Sheds
Retaining Walls
Roof Decks not anchored to Building Structure
Rooftop Air Conditioning Replacement, not involving modification or Removal of Duct Work
Scaffolding (Exterior)
Sidewalk Cafes
Sidewalk Elevators
Sidewalk Sheds, Bridges, and Fences
Signs
Storefront Installation in Existing Masonry Openings
Subdivision of an existing Tax Lot
Temporary Structure Erection (trailers, shanties, etc), supplied with Electric and Water Lines only
Tents
Underpinning of Buildings
Vaults
Water Tank Replacement (Exterior)
Zoning Lot Reapportionment

This information was compiled from DOB OPPN's 1/87, 10/87, and 1/88.

Have a question? E-mail Permitadvisor

Tags: , , ,

Photo credit Hi-Tech Heating and Air Conditioning

Saturday, November 10, 2007

Deck in a Rear Yard?

Above is a view into typical Brooklyn Brownstone rear yards, showing many decks and roof coverings constructed of combustible materials. Often, these structures have not been constructed legally.

Q: What are the legal requirements for the construction of a Deck in the Rear Yard of a Brownstone-type building?

A:
When considering construction of a Deck, it is necessary to comply with the Department of Buildings requirements for Decks. Legalization of existing Decks can be problematic, because many have not been designed by an Architect or Engineer and no Permit was ever obtained. The NYC Department of Buildings is cracking-down on Deck requirements, as they can be hazardous from a structural or fire safety standpoint when constructed improperly. An Illegal Deck can also be a problem when selling a property or applying for a Certificate of Occupancy.

Below is a listing of the basic Deck requirements, distilled from NYC Department of Buildings Memorandums. New Decks would need to comply with the below in order to obtain Plan Approval. Existing Decks needing to be Legalized would have to be modified (as required) to comply with the below:

Definition of a Deck:
A Deck is a raised floor, supported by structural framing above the surrounding ground at the level of the first story of a house. A Deck must be constructed without a roof. An outdoor structure with a roof is not a Deck. It may be considered an additional room, in which case different zoning rules and NYC Building Code provisions will apply.

Deck Requirements:
1 Only a NYS Registered Architect or Professional Engineer may design a Deck or porch. The Department of Buildings must approve the plans and issue a permit before any work begins.

2 Decks must be located at or below the floor level of the first story of a house.

3 A Deck may project up to eight feet (8’) beyond the face of the building into the required thirty foot (30’) rear yard.

4 There shall be no useable building or storage space underneath the Deck.

4 There must be at least three feet (3’) between the Deck and the SIDE or REAR LOT LINE, unless the Deck is constructed of non-combustible materials, such as steel, in which case it may be closer to the Property Lines.

5 All Decks must have a railing at least 42 inches high.

6 Spaces between railings and/or posts can be no greater than five inches.

7 Elevated Decks must be braced at the columns and where the beams and columns connect.

8 Decks must be able to withstand a minimum of 40 pounds per square foot plus the weight of the Deck. This is the same live load required as for the building itself. Thus, a Deck will usually require a structure as robust as that of the main house’s floor construction, rather than the flimsy, under-structured wood Decks that are commonly seen.

9 Decks must be properly anchored to a house or building. Nailing Decks instead of using proper anchors is a common mistake that often leads to accidents and can cause serious injuries.

10 A homeowner may construct a Deck, but is not allowed to perform plumbing or electrical work. If you use a contractor, the contractor must have a Home Improvement Contractor’s License.

Have a Deck question? E-mail Permitadvisor

Thursday, November 08, 2007

What is a Revocable Consent?


Above is an example sketch of Planters on the Sidewalk requiring Revocable Consent


Q: What is a Revocable Consent? What is required to obtain one?

A: When a Building Owner wishes to construct a portion of their building beyond the Front Lot Line or Street Line, they may be required to obtain a Revocable Consent approval to do so.

The Building Code allows certain, limited projections beyond the Street Line, for both above-ground and below-ground projections. These are covered in 1968 Building Code Subchapter4, Articles 8 & 9. See my entry on Projecting Balconies as an example of a permissible projection not requiring a Revocable Consent.

If, however, the Building Owner wishes to construct beyond the limitations specified in the Building Code, they will need to apply for a Revocable Consent through the NYC-Department of Transportation.

A Revocable Consent is a grant by the City to construct and maintain certain structures on, over, or under City Property (usually the Sidewalk or Street). As the name implies, the City may revoke the grant at any time, and thus oblige the Owner to remove the projection.

The Revocable Consent process takes approximately 4-6 months, longer if a Uniform Land Use Review Procedure is required (ULURP). The ULURP Process adds at least 6 months to the process.

Generally, consents are granted for a term of ten years, at the end of which time they may be renewed. Revocable Consents are distributed to several reviewing agencies, all of which must approve the petition:

-Borough President's Office
-DOT Borough Commissioner
-Department of Environmental Protection
-Department of Buildings
-Art Commission
-Local Community Board
-City Council
-Department of City Planning (for ULURP)

A few examples of structures that commonly require Revocable Cosents:

-A Building Cornice projecting more than 10" beyond the Property Line.
-An Outdoor Bench on the Sidewalk
-An Information Kiosk
-Building Steps or Entrance Details which project more than 18" beyond the Property Line
-Exterior Wheelchair Ramps installed on an existing building which project more than 44" beyond the Property Line.
-Canopies, exceeding the size limitations of a standard Canopy.

Tuesday, November 06, 2007

Where are Portable Fire Extinguishers required?


Q: In what Occupancies are Portable Fire Extinguishers required?


A: The following information is to the best of my knowledge, and may have been updated or revised. In addition, there may be some special Occupancies where portable fire extinguishers are required that are not listed below (for instance, at Outdoor Sidewalk Cafes with Gas Heaters) However, the below list is a good starting point:

As per SECTION 15-02 OF TITLE 3 OF THE RULES OF THE CITY OF NEW YORK,

"The owner or occupant of any occupancy or space shall ensure that such occupancy or space is equipped with the portable fire extinguishers as set forth in NFPA Standard 10-1998, except as otherwise required by this subdivision. The NYC FIRE DEPARTMENT may prescribe such other or additional portable fire extinguisher requirements as it determines to be necessary for fire protection purposes, based on the use or configuration of the occupancy or space.

Portable fire extinguishers shall be provided in the following occupancies or spaces:

1. Occupancies or spaces used or classified as OFFICES or PLACES OF WORSHIP, HOTELS and MOTELS shall be provided with one fire extinguisher of minimum 2-A rating for every six thousand (6,000) square feet of floor area or fraction thereof on each floor, except that such a fire extinguisher shall be provided for every twelve thousand (12,000) square feet of floor area or fraction thereof on each floor for occupancies or spaces used as or classified as offices or places of worship in fully sprinklered buildings.

2. ROOMING HOUSES and SINGLE ROOM OCCUPANCIES, as defined in the New York State Multiple Dwelling Law, with over 15 sleeping rooms shall be provided with one fire extinguisher of minimum 2-A rating in the apartment of the manager or the building superintendent.

3. HOSPITALS, NURSING HOMES, HOMES FOR THE AGED, DAY NURSERIES accommodating more than 15 children and asylums shall be provided with one fire extinguisher of minimum 2-A rating for every 2,500 square feet of floor area or fraction thereof on each floor.

4. Places of PUBLIC ASSEMBLY or other occupancies or spaces where 75 or more people congregate, including places for entertainment or amusement, shall be provided with one fire extinguisher of minimum 2-A rating for every 2,500 square feet of floor area or fraction thereof on each floor.

5. Occupancies used or classified as RETAIL STORES or shops shall be provided with one fire extinguisher of minimum 2-A rating for every 2,500 square feet of floor area or fraction thereof on each floor.

6. PIERS, STABLES, WAREHOUSES, MANUFACTURING occupancies and all COMMERCIAL occupancies except stores and office buildings shall be provided with one fire extinguisher of minimum 2-A rating for every 2,500 square feet of floor area or fraction thereof on each floor.

7. Occupancies or spaces used or classified as LUMBER YARDS shall be provided with one fire extinguisher of minimum 2-A rating for every 2,000 square feet of floor area or fraction thereof

8. Occupancies or spaces used or classified as TELEPHONE EXCHANGES shall be provided with portable fire extinguishers suitable for Class A and Class C fires. A fire extinguisher of a minimum 2-A rating shall be provided for every 3,000 square feet of floor area or fraction thereof.

9. STORAGE GARAGES, ELECTRIC POWER PLANTS and occupancies or spaces that manufacture, use or store flammable liquids or mixtures, combustible liquids or mixtures, fats, paints, waxes or similar substances shall be provided with an extinguisher suitable for a Class B fire that shall meet the rating and travel distance requirements for Extra (High) Hazard occupancies as specified in Table 3-3.1 of NFPA Standard 10-1998.

KITCHENS (except those used domestically in residential occupancies, but including those kitchens used communally by the occupants of more than one dwelling unit), shall be provided with an extinguisher suitable for a Class K fire, and shall meet the travel distance requirement of §3-7.2 of NFPA Standard 10-1998. The requirements of sub-paragraph 9 shall be in addition to sub-paragraphs 1-8 of this paragraph."

Contact FDNY with any specific questions, or visit the FDNY Web Site for further information.

Have a question about Fire Extinguishers? E-mail Permitadvisor

Monday, November 05, 2007

What is an As-of-Right Development?

Q: What is an As-of-Right Development?

A: An AS-OF-RIGHT development is a DEVELOPMENT which complies with all applicable zoning regulations and does not require any discretionary action (special permit or variance) by the City Planning Commission or Board of Standards and Appeals for approval.

The significance is as follows:
A Developer acquires a vacant, 2,000 sq ft ZONING LOT in a Residence District which has a Maximum FLOOR AREA RATIO (FAR) of, say 4.0.

To determine the maximum ZONING FLOOR AREA that may be developed on the site, we multiply the LOT AREA (2,000 sq ft) x Maximum FAR (4.0), and we get 8,000 square feet.

When the Developer's Architect files the CONSTRUCTION DOCUMENTS with the NYC Department of Buildings for Plan Approval, the Architect illustrates the above FAR Calculation in his Zoning Analysis.

The NYC Department of Buildings Plan Examiner reviews the plans and finds that the development complies with the applicable FAR requirements. Assuming that the project complies with all other Code and Zoning regulations, the DOB Plan Examiner may APPROVE the Plans, and the Developer may construct the 8,000 sq ft building as-of-right.

It is not necessary for the Developer to seek the additional approval of the City Planning Commission, or of the Local Community Board, or of any other outside party of interest. His development complies with the applicable Zoning Laws currently in force, and he is entitled to build.

There are stories about over-development and upset neighbors witnessing new construction that they find bothersome or too large. Sometimes, it is true, an unscrupulous Developer or Architect has abused the DOB's PROFESSIONAL CERTIFICATION* program or exploited a COMMUNITY FACILITY FAR (when the building is not a Community Facility) or has pulled some other 'fast one' that the DOB is likely to catch. But often, the Development is as-of-right.

-For Residents concerned about over-development, gain an understanding of the Zoning Regulations for your District and lobby your Lawmakers to change the Zoning Regulations. Targeting the Developer will not be fruitful if the development complies as-of-right, the plans are approved, and a Work Permit has been issued.

-For Developers, it would usually be unwise not to maximize the potential Zoning Floor Area of the development site.

*Banks often do not accept plans approved under Professional Certification for development financing.

Have a Zoning question? E-mail Permitadvisor

Tags: , , , ,

Sunday, November 04, 2007

Fire Escapes as a Means of Egress?


Picture of a Fire Escape on an existing Multiple Dwelling

Q: Are FIRE ESCAPES permitted as a second Means of Egress on New or ALTERED Buildings?

A: As per Building Code Section 27-368, the use of Fire Escapes as a second Means of Egress is very limited:

-Fire Escapes are not permitted on New Buildings, with the exception of GROUP HOMES.

-Fire Escapes may be used as exits on buildings that existed on 12/6/1968, when such buildings are Altered, but only with the approval of the DOB Commissioner (sounds like the topic of a RECONSIDERATION)

When an existing building relies on a FIRE ESCAPE as a second Means of Egress, the Fire Escape needs to be retained, unless the building's egress is upgraded in such a way that the Fire Escape is no longer required (for instance, if an additional, compliant INTERIOR STAIR were installed to serve as a second Means of Egress).

Have a question about Fire Escapes? E-mail Permitadvisor

Friday, November 02, 2007

DOT Permit Holiday Embargo


Q: For Department of Transporation Construction Permits, when does the DOT Holiday Embargo/Moratorium start and end? What locations in New York City does the Embargo effect?

A: See below excerpt from the DOT Website. Refer to the Attachment for Streets affected by the DOT Holiday Embargo :

"2007 Holiday Construction Embargo - This embargo applies to NYCDOT Construction Permits.

A special construction embargo is in effect Friday, November 16, 2007 from 6AM to 11:59 PM and from Tuesday, November 20, 2007 6AM through Wednesday, January 2, 2008 11:59PM for the 2007 Holiday Construction Embargo. There will be strict enforcement of this embargo and violators are subject to be
summonsed.

Street and sidewalk construction will be restricted from 6:00 AM to midnight during the upcoming holiday season on the roadways listed below. Any permits issued prior to the date of this notice for work in the areas listed for the Holiday Embargo which do not already have the Embargo Waiver traffic stipulation "410" are hereby voided for the period of Friday November 16, 2007 from 6AM to 11:59 PM and from Tuesday November 20, 2007 6AM through Wednesday January 2, 2008 11:59PM. The permits will be in effect again on January 3, 2008.

All permittees must comply with this embargo unless a special waiver is granted by OCMC. Waiver requests must be filed by November 9, 2007 with the Permit Office by filing a "Request for Roadway/Sidewalk Permits During Embargo Periods" with supporting documentation. Work may only occur from 12:01 AM to 6:00 AM with the issuance of the necessary permits, no Embargo Waiver request is needed for work during these times. Waiver requests should only be submitted for critical reasons for a specific project. If a waiver is granted, you will be notified
to apply for the approved permits.

Necessary measures must be taken to ensure that all streets and sidewalks are in proper condition to allow for the expeditious and safe movement of vehicular and pedestrian traffic. OCMC will also impose similar restrictions on public utilities and private contractors for those roadways that are listed below by borough. Tool carts, cable reels, containers, and material stored on roadways must be removed during the embargo period. Utility cover openings are prohibited on roadways noted below between the hours of 6:00 AM and midnight unless the utility or contractor can prove an emergency exists.

Notice to All Permit Applicants:
Please note that this year, in accordance with § 4. Subdivision (m) of section 2-02 of Title 34 of the Rules of the City of New York which reads "A request for approval to work during an embargo shall be submitted on a form provided by the Commissioner, along with a fee ($135.00) as specified in §2-03 of these rules. Payment of the application fee shall not guarantee that approval to work during the embargo period will be granted and application fee is in addition to any required permit fees".

A copy of the form "Request for Roadway/Sidewalk Permits During Embargo Periods" is attached. All forms must be filed with the required documents (shown on the form) along with the required fee at our Permit Office, 220 Church Street Ground Floor by Friday, November 9, 2007. Waiver requests should only be presented for critical reasons related to your specific project."

Wednesday, October 31, 2007

Intumescent Paint for Fire Protection


Q: What is Intumescent Paint? How do I know if it can be used for my NYC Construction Project?

A: Intumescent means "swelling and charring when exposed to flame". When exposed to fire, the coating will rapidly react, becoming a compact foam, dense carbon char, or similar, to stop fire migration.

Intumescent Paint is a paint coating applied to Structural Members in order to afford them a Fire Resistance Rating. It is ususally employed as a remedial measure to enable exposed (unprotected) structural memebers to achieve a required fire resistance rating.

For instance, exposed wood joists and subflooring might be treated with intumescent paint (rather than installing a fire rated gypsum board ceiling assembly to encapsulate them) to achieve a vertical fire separation rating.

Intumescent Paint products must have an MEA (Materials and Equipment Acceptance) Number to qualify as an approved means of rating structural members. The paint must be applied and utilized in a manner consistent with the MEA Approval.

MEA Numbers for Intumescent Paint may be verified by lookup on the Department of Building Website. Check the MEA Index, and search under the "Fire Protection" heading to find approved Intumescent Paints and their respective MEA Numbers and MEA Approval documents.

The MEA Number must be listed on the DOB Drawings and Construction Documents when filing for approval and permit.

Here is a sample MEA-Approval for an Intumescent Paint product.
***
Photo above of an Intumescent Paint Application from Albi Manufacturing

Wednesday, October 24, 2007

Projecting Balconies

Richard Meier's New Building on Prospect Park showing a nice use of Projecting Balconines beyond the Street Line



Q: Can a Balcony Project beyond the FRONT LOT LINE or STREET LINE? If so, how far?

A: As per the NYC 1968 Building Code, Balconies, including their railings and supporting brackets, may project up to 22 inches beyond the STREET LINE. There are also many Zoning Regulations to consider for Balconies. In most cases, Balconies must be located at or higher than the floor level of the third story of a Building or at least 20 feet above CURB LEVEL. The aggregate length of Balconies cannot exceed 50% of the length of the Building Wall from which they project.

Check the Zoning Regulations for additional Balcony requirements.

Ref: Building Code Section 27-313
Zoning Resolution Section 23-13

Sunday, October 21, 2007

IS THIS A SIGN?


Q: Does the above 'Grand Theft Auto' mural, being painted on the side of a building on Houston Street, count as a Sign for Zoning purposes? Is it subject to the Sign Regulations and Area Limitations of the Zoning Resolution?


A: This is in fact a SIGN, specifically an ADVERTISING SIGN, and it would need to comply with the Advertising Sign regulations for the applicable Zoning District.

Tuesday, October 16, 2007

Roof Access for Interior Stairs

Q: When is it required for INTERIOR STAIRS to provide Roof Access?

A: Interior Stairs shall provide Roof Access as follows:

-At least one Interior Stair shall provide Roof Access in buildings or building sections greater than 3 stories or 40' high, when the roof has a slope of less than twenty degrees. Access to setback roof areas may be through a door or window opening to the roof. Interior stairs extending to roofs shall be enclosed in bulkheads of fire-resistant construction.

-All Interior Stairs in buildings classified in J-1 (Transient Residential) or J-2 (Permanent Residential, 3 or more Dwelling Units), which are more than 2 stories in height, with a roof having a slope of 15 degrees or less, shall provide Roof Access, except where the Stair terminates at a Setback Roof. Stairs shall extend to the roof in bulkheads of fire-resistive construction. Stairs terminating at the level of a setback roof shall provide access to the setback roof areas through a door except where the setback is less than 4' in width and less than 10' in length, as measured from the inside of the parapet wall.

-In buildings or in building sections classified in occupancy group J-1 two stories in height and in occupancy group J-2 three stories in height with not more than one dwelling unit per story with roofs having a slope of fifteen degrees or less, access to the roof shall be provided through a scuttle at least 21" in width and 28" in length. Scuttles shall be located within each stair enclosure with a stationary iron ladder leading to them.

Reference 1968 NYC Building Code Section: 27-375(k) for full details

Monday, October 15, 2007

What is a WIDE STREET?


Prospect Park West in Park Slope, Brooklyn (shown above) is a nice example of a WIDE STREET

Polhemus Place in Park Slope, Brooklyn (shown above) is a nice example of a NARROW STREET

Q: What is the definition of a WIDE STREET? Does street width include the width of the Sidewalk?

A: A WIDE STREET is a Street that is 75' Wide or more. Streets less than 75' wide are NARROW STREETS. When determining Street Width, include the width of the sidewalk. It is important to determine whether your proposed DEVELOPMENT is located on a WIDE STREET or a NARROW STREET, as the FAR and HEIGHT AND SETBACK requirements vary depending on what type of street the DEVELOPMENT SITE is located on.

For the full definition of a WIDE STREET, and many more useful permit definitions, visit our other blog: permitpedia.blogspot.com

Thursday, October 11, 2007

Applicability of NYS Energy Code to NYC Projects

Q: When is the NYS Energy Code applicable to New York City Projects?

A: The following buildings must comply with the noted provisions of the Energy Conservation Construction Code of New York State:

-1- and 2-family detached residential buildings and all residential buildings of three stories or less must comply with Chapters 4, 5 or 6 of the Energy Conservation Construction Code of New York State (ECCCNYS)

-All other buildings, including residential buildings four stories or higher and excluding 1- and 2-family detached residences four stories or higher, must comply with Chapters 7 or 8 of the ECCCNYS

-Except where explicitly stated in the Code, ECCCNYS is not retroactive in existing buildings;

-Additions to existing buildings must comply with the ECCCNYS with respect to new construction;

-Alterations must comply with the Energy Code where 50% or more of any building system or subsystem, measured in appropriate units, is being replaced within any 12-month period, with some exceptions;

-In mixed-use buildings, each major use shall comply with the requirements of its occupancy.

The following buildings are exempt from the provisions of the ECCCNYS:

-Buildings with a peak design rate of nonrenewable energy usage less that 3.4 Btu/h/SF;

-Buildings whose energy usage for heating and/or cooling is entirely supplied from renewable energy sources;

-Historic buildings (see ECCCNYS §101.4.2.3 for detail);

-Nonresidential farm buildings (see ECCCNYS §101.4.2.5 for detail).

All New Building and Alteration Type-I Applications must now include an Energy Code statement on the plans and Applications:

"To the best of my knowledge, belief and professional judgment, these plans and specifications are in compliance with the Energy Conservation Construction Code of New York State, using Chapter ____.”

As of September 4, 2007, the Professional Statement and the Energy Analysis will be listed as a Required Item for New Buildings and Alteration Type 1 projects. Alteration Type 2 and Alteration Type 3 OT projects will have the same listed required items in November, 2007.

Excerpts from DOB Web site

Wednesday, October 10, 2007

Stairs with Handrails on Both Sides?

Q: For an Exit Stair, when is it necessary to provide Handrails on both sides?

A: Stairs 44 inches wide and wider require a handrail on both sides. Stairs narrower that 44 inches only require a handrail on one side.

Stairs more than 88 inches wide need intermediate handrails dividing the stair into widths not greater than 88 inches nor less than 44 inches.

This is as per BC Section §27-375(f)

Wednesday, October 03, 2007

Fire Separations for Cellar Stairs

Q: Do Cellar Stairs need to be fire-separated from Stairs serving upper floors of the building?

A: Yes, Cellar Stairs need to be fire-separated from stairs serving upper-floors of the building, with a minimum of 1-hour fire rated construction and a 3/4-hr fpsc door. Except that this separation is not required in J-3 Residential Buildings (One- or Two-Family Dwellings), and in G-School (Educational) Buildings. Refer to Building Code Section 27-364-Exit Discharge for the exact wording/requirements

Balcony Enclosures?

Q: Is it permitted under any circumstance to enclose a Balcony? If so, are there any special considerations to such enclosures?

A: The Department permits lightweight, readily removable balcony enclosures, not considered a permanent part of the building. This is as per a DOB Memo dated 6/17/1976. Balcony enclosures shall comply with the following criteria:

1. The enclosure must be of lightweight, non-combustible construction.
2. The enclosure assembly must not include masonry or insulation.
3. The enclosure must contain operable windows to provide 10% light and 5% ventilation to both the balcony and the room opening onto the balcony.
4. The existing balcony parapet or railing must remain intact.
5. The enclosure shall be anchored and designed to resist Wind Loads and Lateral Loads.
6. Plumbing, heating, ventilation or air conditioning systems must not extend into the balcony (except for the mandatory retention of balcony drains)
7. Additional dead load consisting of flooring, subflooring or soil shall not be added to the balcony. Furniture shall be restricted to the lightweight "lawn type" variety.

search